Tinkering Around!


 

This implies as bridge supply voltage decreases even minutely, the o/p voltage increases, almost doubles.

 

 

  1. WITH SENSOR CONNECTED BETWEEN 9B , 7B & 5B
  1. Before connecting sensor, adjust HV to about 2 V. connect sensor and adjust HV pot such that voltage between 9B & 7B is 2 V
  2. Connect meter between B/A 4(+) and B/A6(-) and adjust zero pot such that meter reads zero. If reading is negative, turn zero pot clockwise to increase
  3. The useful meter reading range is from 0 to 1 V
  4. 0 is 0% LEL and 1 V is 100% on which OR LED should light up. Adjust A1 , A2 to light up at 0.2 v and 0.6 v respectively.

 

 

 

  1. Expt2:

VHV =2 V between 9B & 7B

VA1=6.76 V (setpoint for A1 using A1 pot) (voltage at pin 2 of IC5B)

VA2= 6.90 V(setpoint for A2 using A2 pot) (voltage at pin6 of IC5B)

V5B= 1 V (measured) (signal voltage)

Voutput (IC3B pin 7 buffer voltage)= 6.13 V

 

OR setpoint= 7.12 V (pin9 of IC5D)(OR opamp)

Ref voltage for IC3C = 6.2 V (pin4 o/p of IC2)

 

 

13. Typical Repair case of AE-4103

In this card, on pressing READ button, FAULT will come, otherwise, PILOT glows without problem. When bench testing, it was also damaging the sensor, though, in control room rack, sensor was not damaged, but FAULT used to come on pressing read.

Solution

The NOR gate IC CD4001 was malfunctioning. The logic was all ok. However, current was leaking to adjacent gates. Therefore, when read button was pressed, 12 V should appear on the o/p pin of gate, instead 8 V was appearing and voltage at other pins were also changing due to internal current leak inside the IC and subsequent loading of the output (the o/p is designed to source only 6.8 ma of current max). This was varying the control voltage at the SMPS IC , hence high voltages were appearing on the output (instead of set 2 volts) and damaging the sensor. Replaced the IC, card works ok now.

 

 

Modified on by MANOJ CHERUKAT

find out if someone is on or off in 14 days on/off

MANOJ CHERUKAT Tags:  on/off days checker vba 14 excel 5 Comments 404 Views

Often it happens that people at home or office want to know whether a person would be on duty or off duty for planning a work or a function at  home etc. 

This software has been developed using Visual basic for applications (VBA) and runs in MS-Excel. Macros will have to be enabled for the file for this software to work.The software takes two inputs:-

(a) The date when the person has joined the shift ( to be entered in B1 cell)

(b) The date when his availability is to be ascertained. (to be entered in B4 cell)

 

After entering this data, click anywhere on the sheet, the result will be displayed in B7 cell and the full shift schedule starting from the date he has joined the shift to the test date period would be available in cell A10 onwards. Presently this will work for people in 14 days on/off shift.

click_here to download the file! Please note that macros have to be made enabled in order for this to work.

Welker Probe (Automatic Insertion Instrument Regulator IRA-4SS)

MANOJ CHERUKAT 245 Views

Welker Probe (Automatic Insertion Instrument Regulator IRA-4SS)

 Welker probe is a tool to sample gas from a pipeline and to present to the Gas Chromatograph system at specified pressure. It has safety features like a pressure release valve which vents excess pressure in case of wrong pressure setting, thus, saving the expensive Chromatograph equipment.

The details of the  welker probe can be found here. The manual to install and retract the probe can be found here

Welker is fitted on top of the Gas line carrying high pressure gas through a flanged socket with Ball valve . The socket is  welded on the pipeline. The ball valve must never be closed during the operation of the sample probe as significant portion of the probe is inserted into the gas line. closing the valve will damage the probe. The Probe has to be retracted from the line before closing the ball valve.

A write-up with pictures can be found here explaining the working of the probe .

 

Troubleshooting:

  1. Sample pressure drops below the preset value to 20 psi to about 3 psi

One reason is choke in the mesh of seat retainer (15) due to solid particles like chemicals and sludge accumulating. Remove the probe as per the removal instructions, and clean the mesh

 

  1. Sample pressure reduces even if the mesh is clean

This happened once because spring (14) lost its tension, it was not apparent but comparing the height to a new spare spring showed about one turn elongation. The spring was changed and sample pressure returned to 20 psi.

 

Modified on by MANOJ CHERUKAT

Understanding the Fisher 3582 positioner

MANOJ CHERUKAT Tags:  fisher instrumentation positioner 3582 242 Views

Fisher 3 that the travel pin remains perpendicular to connector arm during this process


2. tighten the cap nut and re-check the the arm at mid-travel position, if the zero degree marks don't align, repeat the procedure.

 

(b) For special travel pin setting (when travel pin setting greater than total actuator travel):-


The arm will not rotate 30 degrees in one direction as the valve is stroked and therefore the 30 degree marks will fall short of aligning with case index marks. only 

thing, the 'gap' between the index marks on the case and rotary shaft arm should be same in both directions (i.e., while stroking to 0 and 100%). If gap is not the 

same, adjust the pin position as described above to make it same.

 

3. WORKING


Working is as explained in the video and pg 32 in the datasheet. The valve positioner can be used in direct and reverse options. 


4. BEAM ALIGNMENT

 
The beam is leveled at the factory prior to shipment. Once the beam is leveled, no additional leveling should be required unless the
beam pivot pin or the bellows assembly pivot pin are changed, the bellows assembly or range spring (to increase the range from 3-15 psi to 6-30 psi) are replaced, or 

the valve positioner is changed to split range operation.


Names of important components to understand the Alignment:-
see fig-15 
Rotary shaft arm (), nozzle lock nut (), nozzle (), flapper assembly (), follower assembly locknut(),follower assembly (),bellows assembly locknut(),bellows pivot pin

(),beam pivot pin locknut(), beam pivot pin().

procedure for beam alignment given in pg 29 in datasheet.

 

5. CALIBRATION

procedure for calibration given in pg 31 in datasheet, the procedure in brief is given below:- see the actual pic:- positioner-photo

1. Keep the flapper assy at position 6 on the scale and stroke to 50 % of stem travel. if the stem does not match the 50% range, adjust the nozzle and tighten the 

nozzle lock nut.

2. When valve is stroked to zero and if the actuator does not move to the proper end of travel, loosen the nozzle lock nut and adjust the nozzle for zero.

3. When valve is stroked to 100% and if actuator does not move to proper end of travel, adjust the flapper assembly to higher value on the scale to reach 100% or if 

the actuator is already reaching 100% at a lower signal value (say 90% input),then adjust flapper assy to lower value on the scale.

4. If span is adjusted, then re-check for zero adjustment 

5. The positioner will fully vent or pressurize the actuator to supply pressure at the ends of actuator travel when the positioner is
calibrated correctly. Failure to properly calibrate the positioner may result in reduced seat loading


6. MAINTENANCE

6.1 Changing the range spring (pg 36 in datasheet) see FIG-21

The device can operate for supply pressure 3-15 psi and 6-30 psi. The higer range operation (6-30 psi) can be done by changing the range spring.(pg 36 in datasheet)

6.2 Adjusting the flapper pivot (pg 38 in datasheet) fig-20

If the flapper is touching the support or if need is felt to adjust the flapper, all you have to do is to loosen the two nuts (19C) which are marked by paint, push the 

ear (19K) slightly such that the flapper does not touch the support and tighten the two nuts (19C). For more details, follow instruction in page 38 in datasheet

6.3 Replacing the nozzle O ring (pg 38 in datasheet)

 

Modified on by MANOJ CHERUKAT

    • 1
    • 2