P&F Barrier -
KCD2-SR-Ex2.SP - Switch Amplifier
Used for:
- This is an isolated barrier is used for intrinsic safety applications.
- The device transfers digital signals from NAMUR sensors or dry contacts from the hazardous area to the non-hazardous area.
- useful for detecting positions, end stops, and switching states.
- The device output changes the state when the input signal changes the state.
Decoding:
KCD2-SR-Ex2.SP
------------------
K: K-System
------------------
C: Version with removable terminal blocks, 12.5 mm width
------------------
D: DC power supply
------------------
2: 24 V
------------------
SR: Switch amplifier with relay output
------------------
-
Ex: Isolated Barriers, not applicable to Signal Conditioners
------------------
2: Number of channels
------------------
.
SP:Special function, if available
Notes:
- 2-channel
- Dry contact or NAMUR inputs (Signal type Digital Input)
- Relay contact outputs
- Supply Connection either from Power Rail or terminals 9+, 10-
- Line fault detection (LFD)
- Via DIP switches the mode of operation of can be reversed and the line fault detection can be switched off.
- Supply: Connection Power Rail (or) terminals 9+, 10-
- Supply Rated voltage Ur 19-30 V DC
- Rated current Ir ≤ 30 mA
- Input
Connection terminals 1+, 2-; 3+, 4-
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 - 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA - Output
Connection terminals 5, 6; 7, 8
Output I signal ; relay
Output II signal ; relay
Minimum switch current 2 mA / 24 V DC - Ambient temperature -20 - 60 °C